Filling the Gaps in Surge Protection
May 1, 2006 12:00 PM
By Deepak Divan, Professor, Georgia Institute of Technology, Atlanta, and CTO, Innovolt, Atlanta
A new circuit protection technology safeguards equipment against voltage surges and the inrush currents that follow voltage-sag events.
News & Features From Auto Electronics
Committed to improving hybrid electric cars
New Motors for Hybrid Vehicles
Battery Firms Battle for Hybrid Hegemony
Innovative Bipolar Plates for Fuel Cells
See More Headlines
Top Articles
Exploring Current Transformer Applications
Ultracapacitor Technology Powers Electronic Circuits
Buck-Converter Design Demystified
Sensorless Motor Control Simplifies Washer Drives
PET Resources
Buyer's Guide
Conferences
Engineering Jobs
Power Electronics Events
Rent Our Lists
Spotlight on Digital Power
For the PDF version of this article, click here.
Major equipment manufacturers, in fields as diverse as industrial automation, medical electronics and consumer electronics, are seeing 30% to 50% of their field failures resulting from a single root cause. Such field failures typically occur in the input power-supply stage, and have routinely been attributed to “power surges.” The primary form of surge protection today is transient voltage surge suppression (TVSS) to protect against voltage surges that occur as a result of direct lightning strikes.
In spite of the ubiquity of such protection, equipment failures continue, which suggests the root cause has not been identified and addressed. Billions of units of electrical equipment are operating and continue to be deployed worldwide and remain vulnerable to premature failure, resulting in unscheduled downtime and excessive warranty and replacement costs. This points to a possible “gap” in equipment protection, and a need to better understand the root causes for these failures.
This article will analyze the issues related to premature equipment failure and propose a new type of surge-protection device, a current-inrush voltage surge suppressor (CVSS), to provide complete protection for susceptible equipment.
It is commonly believed that equipment damage occurs when a lightning strike on the utility system causes a voltage surge. The standard UL 1449 specifies a 6-kV, 20-µs voltage impulse, as representative of a voltage that can be impressed by a direct lightning strike, and specifies a test protocol.
While lightning strikes on the exposed high-voltage power grid are common, there is little evidence to show that these events frequently translate into destructive voltage surges at the point of use for the vast majority of utility customers — all typically connected at low voltage. Rather, given the high-frequency content of the lightning surge, it is clear that damage can only occur if lightning strikes the power line in the immediate vicinity (approximately 200 m) of a customer's premises. This can have severe consequences, but is very rare and does not account for the much higher incidence of equipment failure that is observed.
Furthermore, deployment of a layered-voltage surge-protection philosophy, including service-entrance protection, theoretically should eliminate the potential for equipment damage, but in practice fails to do so. This may also point to a puzzling phenomenon frequently encountered where equipment connected in close proximity to the damaged unit does not suffer any damage whatsoever. Trying to explain such occurrences has been one of the “mysteries” in the field of surge protection.
The leading cause of equipment failure may not be the voltage surge after all, but rather a current-inrush surge that occurs at the end of frequent voltage-sag events. Let's look at the analysis and evidence supporting this premise, as well as the behavior of typical electronics equipment under voltage-sag conditions. We will also look at how to assess susceptibility to voltage and current-inrush surges.
Root Causes
For almost any piece of electronics equipment, the input rectifier stage consists of a rectifier and a capacitor. This is true for most electronics equipment, including PLCs, robots, medical equipment, drives and consumer electronics equipment. It is well known that startup conditions can cause a current surge that can damage the rectifier, capacitor or fuses. An inrush current limiter, using either a negative-temperature-coefficient (NTC) resistor or a relay-resistor series combination, is commonly used to limit the current drawn at startup and is bypassed for normal operation (Fig. 1).
Any major fault on the power system normally results in a voltage sag that can be measured more than 100 miles from the fault location. When a voltage sag occurs on a utility bus connected to electronics equipment, the line current drawn by the equipment goes to zero as the diode bridge is reverse biased, and the dc bus capacitor begins to discharge slowly. When the fault is cleared, the line voltage abruptly returns to normal, and begins to recharge the dc-bus capacitance with the inrush current limiter bypassed. This then results in a large unprotected current surge that flows into the equipment as shown in (Fig. 2).
Clearly, equipment designers would consider such current surges to be potentially damaging, because they use an inrush current limiter at startup. However, the input power-supply design specification does not typically specify behavior under short-duration voltage sags, almost universally assuming that the voltage will remain within a band of say ±10% of nominal value, or will go to zero and eventually return to a normal startup condition.
Analysis shows that the current-inrush surge can put stress on several power-supply components. While the diode rectifiers can handle large current peak currents, it can be shown that the thermal shock or I
Finally, a resonant charging between the line inductance and the capacitor can cause the surge voltage rating of the capacitor to be exceeded (Fig. 2). Most capacitor vendors specify that a capacitor surge voltage rating can only be exceeded a few times before damaging the capacitor.
Susceptibility of Equipment
The premise that the vast majority of electronics equipment sold today may be unprotected and susceptible to damage from frequently occurring power disturbances might seem unjustifiable. To validate the concept, a cross-section of commercially available equipment and appliances were selected and tested for current-inrush susceptibility.
Fig. 3 shows typical data for current inrush and I
Similar measurements have been done for a wide variety of equipment, including TVs, PLCs and printers, with almost all types of equipment demonstrating significantly higher-than-normal (20 to 50 times greater) current-inrush levels. Calculations also show that the dissipated energy associated with a current surge can exceed that of a voltage surge associated with a lightning strike, showing the potential for significant damage.
Fig. 4 shows a computation of the I
The characteristics in Fig. 4 are similar to the measured data in Fig. 3, and validate the physics behind the underlying phenomenon. It also shows that the I
Similarly, failure modes for the capacitor are seen to depend on the reactance-to-resistance ratio of the ac-line source impedance, and repeated exposure to the rated surge voltage can result in early failure of the device. As the dc power supply is a universal part of all equipment today, and because there are no governing specifications or standards regarding equipment behavior under short-duration voltage sags, it is not surprising that the susceptibility to voltage sags is to be found across all categories and classes of equipment — industrial, medical, commercial and consumer — pointing to the ubiquity of the problem.
If voltage sags rarely occurred, the previous discussion would not be of great significance. On the other hand, if deep and potentially damaging voltage sags and their associated current surges occur frequently, then it is important to find suitable protection. Data from years of power-quality monitoring show that voltage sags are caused by all types of faults, including lightning strikes on the power grid, and occur 100 times more frequently than voltage surges.
Fig. 5 shows a typical recorded voltage profile for a power disturbance measured at a large industrial facility. The voltage sag is clearly seen with a rapid return to normal voltage occurring once the fault is cleared. Extensive data confirms that voltage sags of this type occur 30 to 100 times per annum for all categories of customers connected to the U.S. power grid.
Further analysis shows that 80% of all voltage sags are seen to have at least a 20% jump in voltage as the voltage-sag event ends. This is sufficient to cause a significant current-inrush surge. Larger plants and buildings with connected load of 1 MW to 30 MW tend to have stiffer buses and lower source impedance, resulting in even higher current surges and trapped energy. It should be noted that most light commercial, office and residential customers will see an even higher incidence of voltage sags.
Given the susceptibility of most electronics equipment to current inrush occurring at the end of voltage sags, the relatively high frequency of voltage sags and the inability of existing TVSS devices to protect against such current surges, it is clear there is a need for CVSS, which is cost-competitive with TVSS devices.
Innovolt (Atlanta) has recently introduced the first patent-pending CVSS product in the market. The CVSS protects against both voltage surges and current-inrush surges caused by voltage sags. The current surge limiting function relies on sensing when the ac voltage conditions are likely to result in a current-inrush surge. At such time, the CVSS limits the maximum current allowed until the voltage has returned to nominal conditions. Voltage-surge protection is provided as per UL 1449 requirements.
The product is available in both plug-in as well as hard-wired (with DIN-rail option) formats, presently at current ratings of up to 15 A at 120 Vac, with additional ratings due for release later in 2006. The CVSS also has a built-in data logger to provide a history of the actual power disturbances protected against. Fig. 6 shows a rendering of the plug-in CVSS unit.
The CVSS units have been tested with different loads under normal and abnormal voltage conditions. Fig. 7 shows the current inrush and I
Additional testing of the CVSS with a variety of office, consumer and industrial equipment has confirmed a dramatic reduction in peak currents and I
The solutions are simple to use with no user training required. By providing complete protection in one package, it circumvents the question of whether voltage or current-inrush surges represent a bigger problem for a specific consumer.
While the analysis in this article focused on single-phase input systems, the conclusions generally apply equally to three-phase input systems and systems with active front-end input stages. It has also been shown that current surges at the end of frequently occurring voltage-sag events can result in stresses on the input-stage components that can dramatically exceed their ratings.
Further Reading
More information about the relationship between power quality and equipment failure can be found in the following resources:
-
Divan, D.; Bendre, A.; and Johal, H. “Understanding the Dominant Field Failure Mechansim for DC Power Supplies,” IEEE APEC Conference, Dallas, April 2006.
-
Bendre, A.; Divan, D.; Kranz, W.; and Brumsickle, W. “Equipment Failures Caused by Power Quality Disturbances,” IEEE IAS Conference Record, 2004.
-
McGranaghan, M.; Gunther, E.; and Laughner, T. “Correlating PQ Disturbances with Lightning Strikes,” Power Quality magazine, September 2002, pp. 8-13, 67.
-
Conaster, B.; Nastasi, D.; and Phipps, K. “Following the Trail of Destruction,” Power Quality magazine, September 2002, pp. 62-66.
-
Divan, D. “Evaluating Equipment Susceptibility to Current Surges,” EPRI PQA Conference Presentation, Vancouver, July 2005.
-
Divan, D.; Luckjiff, G.A.; Brumsickle, W.E.; Freeborg, J.; and Bhadkamkar, A. “A Grid Information Resource for Nationwide Real-Time Power Monitoring,” IEEE Transactions on Industry Applications, Vol. 40, Issue 2, March/April 2004, pp. 699-705.